Any successful profibus communications from .NET?


Has anyone successfully talked profibus from a .NET application?

If you did, what device/card did you use to accomplish this, what was the application, and did you use any kind of preexisting or available code?


Solution

  • We've not used Profibus, but have used DeviceNET (another CAN based protocol), Ethernet/IP and ControlNet which all have similar challenges.

    We've been doing this since the late 1990's and therefore rely mainly on our own generated code using off-the-shelf hardware. The companies that have shown longevity during that period that I remember are:-

    I suggest not using OPC interfaces to the hardware directly (it’s OK for communication using PC (.NET)->PLC->Profibus) as you need to ensure that the control system responds to loss of control from your .NET application. I’m assuming that you are needing a profibus Master here (not a slave), so as long as your control system is intrinsically fail safe, then loss of communication should mean the control system enters an "Idle" state and therefore most of the I/O will return to the fails safe state.

    We also try to ensure that we do not put safety related code in .NET. Most of our .NET code is userinterface from a PLC, but in some places we do control the fieldbus directly but ensure hardware interlocks will prevent un-safe operation, either using safety switches/relays or a small PLC with the the task of interlocking only. And above all make the system fail-safe! Loss of comms from the .NET code should shutdown the automation to the fail-safe state.